CCGT vs simple cycle: telling gas plant configurations apart in satellite imagery

If you cover gas-fired generation, you've probably pulled up a plant on satellite imagery and had to guess at its configuration before you could even start modeling heat rate or dispatch behavior. Nameplate capacity alone doesn't tell you whether you're looking at a combined cycle (CCGT) unit running a heat recovery steam generator off the back of its gas turbines, or a simple cycle peaker that's just gas turbines and exhaust, no steam loop at all. The good news is the physical plant layout gives this away pretty reliably once you know what to look for.
The stack count and shape is your first tell
Simple cycle plants exhaust directly. Each gas turbine vents through its own stack, usually short and wide relative to a CCGT stack, because there's no HRSG backpressure to manage and no SCR/CO ductwork running horizontal before the exhaust turns vertical. Count the stacks against the number of turbine enclosures you can see. A one-to-one ratio of turbine buildings to stacks, with stacks that look stubby and close to the turbine hall, points toward simple cycle.
CCGT plants route exhaust through an HRSG before it reaches the stack. From above, the HRSG reads as a long rectangular structure, often taller than the turbine building itself, sitting between the gas turbine enclosure and the stack. The stack itself tends to be taller and narrower than a simple cycle stack, since it's venting post-HRSG flue gas rather than raw turbine exhaust. Tracing a turbine building into a boxy intermediate structure and then into a tall stack marks a combined cycle train.
Cooling infrastructure confirms it
This is the part most analysts rely on day to day, because it's visible from a wider shot without needing to zoom into individual stacks. CCGT units run a steam turbine off the HRSG, and that steam cycle needs cooling. You'll see either a cooling tower (the classic hyperboloid or linear mechanical-draft rows) or a large footprint of air-cooled condenser fins laid out in a grid, usually elevated on a structural deck. Simple cycle plants have no steam cycle and no rejected heat to manage this way. A gas plant site with turbine buildings, stacks, and nothing resembling cooling towers or ACC decks is almost always simple cycle.
Watch for the hybrid case too. Some sites run a mix, simple cycle peakers co-located with a CCGT block added later for baseload economics. In those cases you'll see both signatures on the same parcel: a cluster of stubby stacks on one side, an HRSG-and-tall-stack train with a cooling tower or ACC deck on the other. Treating the whole site as one configuration will throw off your capacity factor assumptions, so it's worth mapping each train separately when the layout supports it.
Why this matters for your week-to-week read
Configuration identification is a one-time exercise per plant, but it sets up everything you do afterward. Once you know you're tracking a CCGT train, the HRSG stack and the cooling tower plume become your two signals to watch together. Steam without a corresponding stack heat signature usually means the HRSG is bypassed or the unit is running simple-cycle-only during a steam-side outage. On a true simple cycle peaker, you're reading stack activity in isolation, since there's no cooling signature to cross-check against.
That's the layer FlyPix was built for once you've got the configuration pinned down: a weekly read on stack and cooling-water activity at a named plant, charted out so you can see it move against generation and gas-demand data instead of waiting on the next EIA filing. Start with the configuration tells above, then check the weekly activity nowcast page to see what tracking a specific plant's imagery signature over time looks like.